Duct leakage tester

Duct leakage tester

Duct leakage tester

Art.nr: 765902 [View large]
• Stable pressure control

765902 Leakage tester 22...120 l/s (at ±400 Pa)
770890 Orifice plate 1...4 l/s (at ±400 Pa)
770900 Orifice plate 4...33 l/s (at ±400 Pa)

The leakage tester consists of an adjustable fan with frequency converter and a measuring pipe. The unit is connected to a universal instrument Swema 3000md with built-in pressure sensor and a connected external pressure sensor SWA 10.

Swema 3000md controls the frequency converter which in turn regulates the fan up to 60 Hz. In Swema 3000md you set the pressure you want to test the duct. Once the desired pressure is reached, a measurement protocol can easily be saved in Swema 3000md and then printed. If the test duct enclosure area and density class are entered into the instrument, it is shown directly in the display whether the tightness of the channel is approved or not.

The built-in pressure sensor in Swema 3000md measures the pressure in the ventilation duct against which the fan is regulated. The connected pressure sensor, SWA 10, measures the leakage flow across the measuring pipe. A fixed mounted orifice plate with k-factor in the measuring tube gives the flow. For smaller flows there are two alternative orifice plates with smaller holes available as accessories, that easily are mounted with screws in the measuring pipe.

The fan used is a radial fan whose characteristics make it possible to build up a high pressure. The stated measurement uncertainty applies between 0...850 Pa duct pressure, but a duct pressure up to 1900 Pa is possible.

The section of the ventilation ducts to be tested is sealed with sealing bladders.
With an anemometer or with a smoke pen you can locate leaking air.

The leakage meter is used for leakage testing of ducts according to European Standard: EN 12237 and EN 1507 up to a duct pressure of 1900Pa.

Instrumentation:
Duct leakage tester (765902)
Orifice plate (770960)
Orifice plate (770970)
Swema 3000md (764202)
SWA 10(761430)
Holder(764760) 2pcs, to attach SWA 10 to Swema3000md
Stop (764870) 1pc, to prevent SWA 10 from sliding on Swema3000md
Silicon hose (762470) 8m, between tester and Swema 3000md and duct

Accessories:
Bladder dia 250mm (765080) To seal duct, as many as needed
Bladder dia 400mm (765090) To seal duct, as many as needed
Bladder dia 600mm (765100) To seal duct, as many as needed
Pump (766620) Pump with connector to pump up bladders by hand

Duct Leakage Tester Manual.pdf (to be updated)



Flow over / under pressure
Leakage tester with hose Ø100mm:
22...120 l/s at ±400 Pa duct pressure
C-class Duct area 95...800 sqm at 400 Pa (EN 12237, 1507)
25...103 l/s at +850 Pa duct pressure

Lower duct pressure extends the flow range.

Uncertainty: ±6,5% read value (when used together with Swema 3000md and SWA 10)

95% coverage probability in non condensing, non moist air, <80%RH, non aggressive gases

Weight: 18kg
Hose, diameter: Ø100 mm
Power: 0,37 kW
Supply: 200-240 VAC +/-10%, 50-60 Hz

Leakage tester


Swema ABVAT No. 556052-5551

Pepparvägen 27 123 56 Farsta