Duct leakage tester

Duct leakage tester

Duct leakage tester

Art.nr: 765900
• Stable pressure control

765900 22...120 l/s (at ±400Pa)
765901 4...33 l/s (at ±400Pa)
This leakage tester for ducts connects to a Swema 3000md with SWA 10. Swema 3000md controls the tester to test at selected pressure level between -850 and 850Pa. A leakage level is saved together with the pressure level.

The Swema 3000md inbuilt differential pressure sensor measures the over pressure in duct and SWA 10 measures the leakage flow over a throttle device with a certain k-factor.

An radial fan is used to be able to provide highest possible pressure at these moderate air flows.

Tighten the ventilation supply and exhaust with tightness bladders.

The duct leakage tester is used according to European standard EN 12237 and EN 1507 up to a limited pressure of 1500 Pa.

Instrumentation:
Duct leakage tester (765900)
Swema 3000md (764202)
SWA 10(761430)
Holder(764760) 2pcs, to attach SWA 10 to Swema3000md
Stop (764870) 1pc, to prevent SWA 10 from sliding on Swema3000md
Silicon hose (762470) 8m, between tester and Swema 3000md and duct

Accessories:
Bladder dia 250mm (765080) To seal duct, as many as needed
Bladder dia 400mm (765090) To seal duct, as many as needed
Bladder dia 600mm (765100) To seal duct, as many as needed
Pump (766620) Pump with connector to pump up bladders by hand

Duct Leakage Tester Manual.pdf



For model 765900:

Flow over pressure
Leakage tester with hose Ø100mm:
14...122 l/s at +400 Pa duct pressure
C-class Duct area 95...800 sqm at 400 Pa (EN 12237, 1507)
25...103 l/s at +850 Pa duct pressure


Flow under pressure
Leakage tester with hose Ø100mm:
22...120 l/s at -400 Pa duct pressure
C-class Duct area 150...800 sqm at 400 Pa (EN 12237, 1507)
32...95 l/s at -850 Pa duct pressure

Lower duct pressure extends the flow range.

Uncertainty: ±6,5% read value (when used together with Swema 3000md and SWA 10)

95% coverage probability in non condensing, non moist air, <80%RH, non aggressive gases

Weight: 18kg
Power: 0,37 kW
220VAC supply

Leakage tester

×


Swema ABVAT No. 556052-5551

Pepparvägen 27 123 56 Farsta


Phone: +468 - 94 00 90

Fax: +468 - 93 44 93